Coil Company Chilled Water Horizontal Belt Drive Air Handler

Overview

Cabinet - Heavy-gauge galvanized steel insulated with 1/2” thick, over three pound density, neoprene coated fiberglass.
Coils - 1/2” OD copper tube with aluminum fins (12FPI) equipped with manual-air vent. Coils are 100% underwater pressure tested at 350 PSI with a 300 PSI working pressure.
Drain Pan - Galvanized and powder coated epoxy with a 1/4” thick closed-cell insulation and has primary and secondary drain connections.
Blower & Assembly - Belt-driven draw-through design with forward-curved and dynamically balanced blowers. Adjustable, variable-pitch drive sheave and cast-iron pulley keyed to motor shaft.
Controls - Controls and motors are factory-wired and terminated in a junction box for single-point power supply.
Filter - Two-inch thick, 30/30 pleated filter, flatly mounted, with spring loaded clips on each side of the access door for easy maintenance without the use of tools.
Added Features - Each unit is tagged and crated as scheduled for installation.
Certification - UL and cUL approved, ARI certified and 100% factory tested.

Click here to browse all the Coil Company equipment Control Specialties offers.