The Walchem Contacting Conductivity Sensor are ideal for use in cooling towers and boilers, reverse osmosis equipment, and other non-oily applications. A variety of cell constants are available to handle a range of conductivities.

Need additional assistance? CONTACT US

Walchem Contacting Conductivity Sensors measure conductivity of a solution via electrodes. They are ideal for use in cooling towers and boilers, reverse osmosis equipment, and other non-oily applications. A variety of cell constants are available to handle a range of conductivities. They are available in several different configurations:

Cooling Tower Contacting Conductivity Sensors- These cell constant 1.0 sensors are designed for cooling towers with water up to 30,000 μS/cm. Lower pressure (up to 150 PSI, 10 atm) polypropylene sensors are available with graphite or stainless steel, and may be installed inline or submersion. High pressure (up to 300 PSI, 20 atm) inline sensors are constructed from stainless steel and PEEK.

Boiler Contacting Conductivity Sensors- These cell constant 1.0 sensors are designed for boilers with water up to 10,000 μS/cm and pressure (up to 250 PSI, 16.7 atm). These inline sensors are constructed from stainless steel and PEEK.

General Purpose Contacting Conductivity Sensors (for W100/600/900 Series)- These passive sensors are available in a variety of cell constants for use in conductivities up to 300,000 μS/cm. Typical applications include RO systems and boiler condensate monitoring. They may be mounted inline or submersion, using either polypropylene or stainless steel 1/2" NPT mounting fittings.

Cell Contacting Conductivity Range Resolution Accuracy
0.01 0 - 300 µS/cm 0.01 µS/cm, 0.0001 mS/cm, 0.001 mS/m, 0.0001 S/m, 0.01 ppm ±1% of reading
0.1 0 - 3,000 µS/cm 0.1 µS/cm, 0.0001 mS/cm, 0.01 mS/m, 0.0001 S/m, 0.1 ppm ±1% of reading
1.0 0 - 30,000 µS/cm 1 µS/cm, 0.001 mS/cm, 0.1 mS/m, 0.0001 S/m, 1 ppm ±1% of reading
10.0 0 - 300,000 µS/cm 10 µS/cm, 0.01 mS/cm, 1 mS/m, 0.001 S/m, 10 ppm ±1% of reading

Note:Conductivity ranges above apply at 25°C. At higher temperatures, the range is reduced per the range multiplier chart.

Temperature °C Range Multiplier %
0 181.3
10 139.9
15 124.2
20 111.1
25 100
30 90.6
35 82.5
40 75.5
50 64.3
60 55.6
70 48.9
80 43.5
90 39.2
100 35.7
110 32.8
120 30.4
130 28.5
140 26.9
150 25.5
160 24.4
170 23.6
180 22.9

 

Need additional assistance? CONTACT US