Watson McDaniel 1041 Inverted Bucket Steam Trap
Product Shipping Subject to Factory Availability Need Specifications? See PDF Section Below.
Need additional assistance? CONTACT US
The Watson McDaniel IB Series inverted bucket traps are available in several sizes and capacity ranges. Inverted bucket traps can handle superheated steam when a check valve is used. The smaller traps are primarily used in drip and tracer applications. These traps are also used on unit heaters, laundry equipment, and other process equipment where slow start-up due to poor air handling capability can be tolerated. Larger sizes are used on process equipment; however, since bucket traps have limited air handling capability, F&T traps are the preferred choice.
HOW IT WORKS
When there is condensate in the system, the inverted bucket inside the steam trap sits on the bottom of the trap due to its inherent weight. This allows condensate to enter the trap and to be discharged through the seat orifice located at the top. When steam enters the trap, the bucket floats to the surface and closes off the discharge valve containing the steam in the system. Eventually steam is bled off through a small hole in the top of the bucket causing the bucket to sink which repeats the cycle.
FEATURES
* Handles superheated steam (use internal check valve option to eliminate loss of prime)
* Water hammer resistant
* In-line repair-ability is simplified by having all internals attached to the cover
* Valve & seat are at the top of the trap making it less sensitive to dirt
* All stainless steel internals with hardened valve & seat
INSTALLATION
Trap must be installed in upright position to function properly.
MAINTENANCE
All working components can be replaced with the trap body remaining in-line. The repair kit for the traps contain a lever and seat assembly with gasket. If a new trap is required, remove and replace. With superheated steam, a check valve must be installed at inlet of trap. For full maintenance details see Installation and Maintenance Manual.